- Series: WSRA Series
- Operational Settings: Occupancy Time Delay, On Mode, Switch
- Modes, Darkness Set-Point, Photocell Mode, LED Operation, Manual On
- Grace Period, Predictive Exit Time, Predictive Grace Time, Fade On Rate
Occupancy Time Delay:
The occupancy sensor can be set to keep the lights on for different durations after detecting occupancy. Adjust the setting as per your preference.
Bekapcsolt módban:
Choose between Automatic On, Manual On, or Reduced Turn-On modes based on your requirements. Automatic On turns the lights on automatically upon occupancy detection, Manual On requires manual intervention to turn the lights on, and Reduced Turn-On initially ignores small motions.
Üzemmódok váltása:
Switch between different modes such as Switch Disable, Predictive Mode, and Predictive Mode with Expiration. These modes control how the sensor operates after a certain period of inactivity.
Darkness Set-Point / Inhibit Set-Point:
Set the ambient light level at which the lights will be adjusted to the High Trim setting. The Set Now option automatically selects the Darkness Set-Point based on current conditions in the room.
Fotocella mód
Enable or disable the feature that prevents lights from turning on when the light level is above the Inhibit Set-Point.
Alapértelmezések visszaállítása
Reset all functions to their original settings if needed.
LED működés
Select the behavior of the device’s LED indicator.
Manual On Grace Period
Set a grace period for manual control of the lights when in Manual On mode.
Predictive Exit Time and Predictive Grace Time
Adjust the time intervals for predictive exit and grace periods when occupants leave the room.
Fade On Rate
Set the time required for the lights to reach their preset brightness level.
Operational settings
Occupancy Time Delay:
Az az időtartam, ameddig a foglaltságérzékelő égve tartja a világítást, miután utoljára észlelte a foglaltságot.
| Beállítás | Foglaltsági idő késleltetése |
|---|---|
| 1 | 30 mp |
| 2 | 2.5 perc |
| 3 | 5.0 perc |
| 4 | 7.5 perc |
| 5 | 10.0 perc (alapértelmezett) |
| 6 | 12.5 perc |
| 7 | 15.0 perc |
| 8 | 17.5 perc |
| 9 | 20.0 perc |
| 10 | 22.5 perc |
| 11 | 25.0 perc |
| 12 | 27.5 perc |
| 13 | 30.0 perc |
3=On Mode
Nem alkalmazható Vacancy (VA) opció esetén
Automatikus Be
Az érzékelő automatikusan felkapcsolja a világítást, ha foglaltságot észlel.
Kézi Be
Az érzékelőnek meg kell nyomnia a gombot a világítás bekapcsolásához.
Csökkentett bekapcsolás
Az érzékelő kezdetben csak a nagy mozgásokat érzékeli, gyakorlatilag figyelmen kívül hagyva a visszavert passzív infravörös (PIR) jeleket. A bent tartózkodókat továbbra is azonnal észleli, amikor belépnek a helyiségbe, mivel nagy a PIR jelük. Amint a fények világítanak, az érzékelő visszatér a maximális érzékenységre.
- Automatikus Be
- Csökkentett bekapcsolás
- Manual On ‘
4=Switch Modes
Nem alkalmazható Vacancy (VA) opció esetén
Kapcsoló engedélyezése (felülbírálás ki)
Button will turn lights And keep them off until pressed again. The lights will remain off until the button IS pressed again, resetting the sensor to Automatic On mode.
Kapcsoló tiltása
A felhasználó nem kapcsolhatja le a világítást a nyomógombbal.
Prediktív mód
Pressing the push-button switch turns the lights off and temporarily disables the occupancy detection. After 10 seconds, the occupancy detection reactivates am mmttors for an additional 30 seconds. no «upancyls detected during this period” the sensor will revert to Automatic On operation. If occupancy is detected the sensor will remain in Override Off mode and requires the switch to be pressed in order to restore the sensor to Automatic On.
Predictlve Mode wdth Expiratlon
Pressing push-button switch turns the lights off and temporarily disables the occupancy detection. After 10 s«mds, the occupancy detection reactivates am mmltors for an additional 30 seconds If no occupancy is detected during this period” the gnsor WII/reverts to Automatic On operation.
- Kapcsolja be
- Kapcsoló tiltása
- Prediktív mód
- Predictive Mode with Expiration.
5=Darkness Set-Point / Inhibit Set-Point
Az a környezeti fényszint, amelyen az érzékelő a világítást High Trim beállításra állítja.
| Beállítás | Light Level (fc) | Megjegyzések |
|---|---|---|
| 1 | Set NOW* | Default/current setting |
| 2 | 0.1 fc | Very low light |
| 3 | 1 fc | Gyenge fény |
| 4 | 4 fc | Moderate low light |
| 5 | 8 fc | Közepesen világos |
| 6 | 16 fc | Medium-high light |
| 7 | 24 fc* | Default recommended |
| 8 | 32 fc | Erős fény |
| 9 | 48 fc | Nagyon világos |
| 10 | 64 fc | Kiemel |
| 11 | Le | Light level off |
| 12 | 96 fc | Maximum standard brightness |
| 13 | 128 fc | Extra bright |
| 14 | 192 fc | Rendkívül fényes |
| 15 | 256 fc | Maximális beállítás |
Set Now will automatically select the Darkness Set-Point based on the current conditions in the room. Lights will go to full bright and sensor will rapidly flash for 15 seconds, allowing the occupant to move out of direct view az érzékelőtől. Amint az alapjel kiválasztása befejeződött, az érzékelő duplán villog a megerősítésként.
7=Photocell Mode
Csak gátlás
Prevents lights from automatically coming on when light level is above the Inhibit Set-Point
- Letiltva
- Csak gátlás
9=Restore Defaults
Returns all functions to their original settings.
- Aktuális fenntartás*
- Alapértelmezések visszaállítása
11=LED Operation
Indicates behavior of the device’s LED.
- Foglaltság jelzése*
- Letiltva
14 = Kézi türelmi idő
Time period after lights automatically turn off that tho can be reactivated by motion, Applicable only when sensor is in Manual On (Semi Auto) mmie.
- I-Osec
- 3-15see
17 = Prediktív kilépési idő
Time period after manually switching fights off to leave the space. Applicob/e onbe when sensor in Predictive Off mode.
- I-5s«
- 2-6 másodperc
- 3-7s«
- 4-8 másodperc
- 5-9 másodperc
- 6-10K*
- 7-15K
- 8-20 másodperc
- 9-30K
18 = Prediktív kegyelmi idő
Time period after Predictive Exit Time fiat sensor rescans the RMRN for remaining occupants. Applicable only when sensor is in Predictive Off mode.
- I-Osec
- 2-5s«
- 3-10K
- 4-20 mp
- 5-30see
- 6-40K
- 7-50 mp
- 8-60 másodperc
19 = Fade On Rate
Time required for light to reach preset IceL
- 1-0.75 see
- 2-25 másodperc
- 3-5 másodperc
- 4-15s«
20 = Fade Off Rate
Time required for light to turn Off
- 1-0.75 mp
- 2-15see
- 3-5 másodperc
- 4-15 másodperc
HASZNÁLATI BEÁLLÍTÁSI ÚTMUTATÓ
PLEASE READ A1 1 7 STEPS BEFORE PROGRAMMING
- Enter programming mode by pressing & holding button until LED flashes rapidly. Release button.
- Enter a specific function by pressing button. The number Of times as the desired function number from the tables on the following pages (e.g., press twice for function 2, Occupancy Time Delay).
- The selected function’s current setting will then be read out in a sequenæ of LED flashes (e.g., five flashes for 10 min). TO change setting, proceed to step 4 before sequence repeats 10 times.
- While the sensor is flashing back current setting, interrupt it by pressing button the number of times for the new desired setting as indicated in the particular function’s detailed table (e.g., press seven times for 15 min). Sensor will begin to flash new setting as confirmation.
- Next, while the sensor is flashing back new setting, interrupt it by pressing and holding button until LED flashes rapidly. Release button.
- As final confirmation and activation Of the new setting, re-enter the function number that was changed (e.g., press twice for function 2, Occupancy Time Delay).
- LED will flash twice indicating acceptance of new setting. If two flashes are not seen, repeat 7 step process

Jegyzet:
TO exit programming mode without saving or to change to a different function, wait for the blink back sequence to repeat 10 times, then return to step 1.
GARANCIA
5 év korlátozott garancia. A teljes körű garanciális feltételek a címen találhatók www.acuibrands.com/CustomerResourcesTerms_and_conditions.as x
OLVASSA EL ÉS KÖVESSE MINDEN BIZTONSÁGI UTASÍTÁST!
ŐRIZZE MEG EZEKET AZ UTASÍTÁSOKAT, ÉS A TELEPÍTÉS UTÁN SZÁLLÍTSA A TULAJDONOSNAK
- Acuity Brands I One Lithonia Way Conyers, GA 30012
- Telefon: 800.535.2465 www.acuitybrands.com/sensorswitch @2014-2021 Acuity Brands Lighting, Inc.
- All rights reserved. Rev. 09/27/21 lofl 912-00262-002
GYIK
How do I reset all settings to default?
Navigate to the Restore Defaults option and select 'Restore Defaults' to reset all functions to their original settings.
Dokumentumok / Források
![]() |
sensor switch WSRA Series Wall Switch Sensor with Occupancy [pdfTelepítési útmutató is-wsra 220VAC Edits V5, WSRA Series Wall Switch Sensor with Occupancy, WSRA Series, Wall Switch Sensor with Occupancy, Switch Sensor with Occupancy, Sensor with Occupancy |